Biffa Waste Management — 11kV 2.5MVA Transformer Upgrade
When a cast resin transformer failed in service, the site needed more than a like-for-like swap. It was replaced with a 2.5 MVA amorphous-core transformer filled with MIDEL 7131, plus new cabling, secondary containment and modifications to the existing LV panel.
The incoming supply served process plant, materials handling, extraction and site services. When the cast resin unit failed, production stopped. On a waste site that is not a clean indoor problem: incoming waste keeps arriving, odour and fire risk rise, and throughput contracts are immediately at risk.
Cast resin is often chosen for fire performance and the lack of insulating liquid. On this kind of site it is still a hard environment — dust, moisture, corrosive air, vibration from shredders and conveyors, and thermal cycling. Partial discharge, surface tracking and winding hot spots can build with little warning.
A second dry-type unit would have restored power. It would not have fixed the atmosphere, future load, standing losses, or the state of the tails and LV incoming cell.
A 2.5 MVA sealed liquid-filled unit with:
On a continuously energised 2.5 MVA transformer the no-load improvement is typically tens of MWh a year.